User guide

Publication 900-UM007D-EN-E - January 2011
Parameter Adjustments & Application Considerations 4-49
Parameters Related to Loop Break Alarms
Set NONE as the unit for analog inputs.
A loop break alarm can be output by setting the Alarm 1 Type to 12
(LBA).
A setting of 12 (LBA) can be configured for Alarm 2 or 3 but the setting
will be disabled.
Loop breaks are not detected during SP Ramp operation.
Loop breaks are not detected during Auto-Tuning, Manual operation, or
while the controller is stopped.
If the Alarm 1 Latch parameter is configured to ON, the latch will be
effective for the loop break alarm.
Automatically Setting the LBA Detection Time
The LBA Detection Time is automatically configured by Auto-Tuning.
(However, it is not configured automatically for heating/cooling
control.)
If the optimum LBA Detection Time is NOT obtained by Auto-Tuning,
configure the LBA Detection Time parameter (Advance Setting
function group).
Table 4.AB
Parameter Name Symbol Sensor Type
Configurable Range
(Units)
Application
Considerations
LBA Detection Time lba
0…9999 (s)
Setting 0 disables the LBA
function.
LBA Level lbal Controllers with
Thermocouple and
Resistance Thermometer
(RTD) inputs
0.1…999.9 (°C/°F) Default: 8.0 (°C/°F)
Controllers with Analog
Inputs
0.01…99.99 (%FS) Default: 10.00% FS
LBA Band lbab Controllers with
Thermocouple and
Resistance Thermometer
(RTD) inputs
0.0…999.9 (°C/°F) Default: 3.0 (°C/°F)
Controllers with Analog
Inputs
0.00…99.99 (%FS) Default: 0.20% FS