Configuration & Basic Operation 3-37
When there are large variations in ambient temperatures due to factors
such as seasonal changes or differences between day and night
temperatures
When there are large variations in air flow in the control cabinet
When heater characteristics change depending on the control system
temperature
When an actuator with disproportional I/O, such as a
phase-control-type power regulator, is used
When a heater is used with fast response characteristics
When the control object or sensor has slow response
When hunting occurs in AT or ST for any reason
Note: PID constants are initialized to the factory settings when switching to
RT. When RT is selected, the derivative time setting unit becomes
second.
RT Features
Even when hunting occurs for PID constants when AT or ST is
executed in normal mode, it is less likely to occur when AT or ST is
executed in RT mode.
Figure 3.71 — Hunting
When the temperature (PV) falls short of the set point for the PID
constants when using AT or ST in normal mode, executing AT or ST in
RT mode tends to improve performance.
Temperature Temperature
Hunting occurs
Set point value
Set point value
Start of control Start of control
Time Time
Hunting is reduced using RT