User guide
Publication 8720MC-IN002A-EN-P — December 2002
2-14 Commissioning Your 8720MC Analog Drive
Refer to the tables below for the linking relationship between the
8720MC I/O event variables and the digital output parameters.
Scaling of Auto Velocity
Analog Reference
This section provides the information you need to scale an auto
velocity analog reference. The default setting is 1000 rpm/10V.
To change the scale factor for the auto velocity analog reference,
perform the following procedure:
1. At the HIM, press the escape key get to the top level display then
depress ENTER. A message similar to the following appears:
2. Press either the up or down arrow key until the following appears:
3. Press ENTER. Press either the up or down arrow key until the
following appears:
Sinks Typical Sources
Parameter
Number
Parameter
Parameter
Number
Parameter
663 Digital_Output_2
Link
330 At Programmed Speed
664 Digital_Output_3 331 Zero Speed
665 Digital_Output_4 332 Motor Speed Below Threshold
666 Digital_Output_5 334 Torque Above Limit
667 Digital_Output_6 335 Velocity Above Limit
668 Digital_Output_7 336 In Position
669 Digital_Output_8 339 Speed Below Minimum
670 Digital_Output_9 340 Speed Above Maximum
671 Digital_Output_10 526 High Winding Enable
527 Low Winding Enable
528 Enable Brake Solenoid
529 Auto Reference Enabled
530 Manual Mode Selected
583 Orient Complete
615 Shut Down Error
Choose Mode
Display
Choose Mode
Program
Choose File
I/O Interface