2-28 Local Panel User Interface
865-UM001A-EN-P – July 2009
EXTENSION PORT X4 (pins 7, 8 and 5)
• Communication protocol for extension port X4 [Protocol].
• Message counter [Msg#]. This can be used to verify that the
device is receiving messages.
• Communication error counter [Errors].
• Communication time-out error counter [Tout].
• Information of bit rate/data bits/parity/stop bits.
This value is not directly editable. Editing is done in the
appropriate protocol setting menus.
MODBUS
• Modbus address for this slave device [Addr]. This address has to
be unique within the system.
• Modbus bit rate [bit/s]. Default is "9600".
• Parity [Parity]. Default is "Even".
For details see the technical description part of the manual.
EXTERNAL I/O protocol
This is a Modbus master protocol to communicate with the
extension I/O modules connected to the extension port. Only one
instance of this protocol is possible.
• Bit rate [bit/s]. Default is "9600".
• Parity [Parity]. Default is "Even".
For details see the technical description part of the manual.
SPA BUS
Several instances of this protocol are possible.
• SPABUS address for this device [Addr]. This address has to be
unique within the system.
• Bit rate [bit/s]. Default is "9600".
• Event numbering style [Emode]. Default is "Channel".
For details see the technical description part of the manual.
IEC 60870-5-103
Only one instance of this protocol is possible.
• Address for this device [Addr]. This address has to be unique
within the system.
• Bit rate [bit/s]. Default is "9600".
• Minimum measurement response interval [MeasInt].
• ASDU6 response time mode [SyncRe].
For details see the technical description part of the manual.
IEC 103 DISTURBANCE RECORDINGS
For details see the technical description part of the manual.
Configuration and
Parameter Setting
(cont.)