Manual

2-26 Local Panel User Interface
865-UM001A-EN-P – July 2009
TRANSFORMER SETTING
Rated voltage in IL side (typically high voltage side)
Rated voltage in I’L side (typically low voltage side)
Rated power of transformer
Connection group of transformer
Zero current compensation in IL side (If transformer is earthed in
IL side, this must set as “ON”)
Zero current compensation in I’L side (If transformer is earthed
in I’L side, this must set as “ON”)
Connection group of the unit transformer, if any. IEC marking
with capital letters Y and D for HV side and small case letters y
and d for LV side combined with the dial hour is used. For
example Yd11 means a wye-delta transformer where the delta
side phase-to-ground voltages are leading 30° the wye side
phase-to-ground voltages.
DEVICE INFO
Relay type (Type ALLEN BRADLEY 865)
Serial number (SerN)
Software version (PrgVer)
Bootcode version (BootVer)
DATE/TIME SETUP
Day, month and year (Date)
Time of day (Time)
Date format (Style). The choices are "yyyy-mm-dd",
"dd.nn.yyyy" and "mm/dd/yyyy".
CLOCK SYNCHRONISATION
Digital input for minute sync pulse (SyncDI). If any digital input
is not used for synchronization, select "".
Daylight saving time for NTP synchronization (DST).
Detected source of synchronization (SyScr).
Synchronization message counter (MsgCnt).
Latest synchronization deviation (Dev).
The following parameters are visible only when the access level is
higher than "User".
Offset, i.e. constant error, of the synchronization source (SyOS).
Auto adjust interval (AAIntv).
Average drift direction (AvDrft): "Lead" or "lag".
Average synchronization deviation (FilDev).
Configuration and
Parameter Setting
(
cont.
)