Manual
2-26 Local Panel User Interface
865-UM001A-EN-P – July 2009
TRANSFORMER SETTING
• Rated voltage in IL side (typically high voltage side)
• Rated voltage in I’L side (typically low voltage side)
• Rated power of transformer
• Connection group of transformer
• Zero current compensation in IL side (If transformer is earthed in
IL side, this must set as “ON”)
• Zero current compensation in I’L side (If transformer is earthed
in I’L side, this must set as “ON”)
• Connection group of the unit transformer, if any. IEC marking
with capital letters Y and D for HV side and small case letters y
and d for LV side combined with the dial hour is used. For
example Yd11 means a wye-delta transformer where the delta
side phase-to-ground voltages are leading 30° the wye side
phase-to-ground voltages.
DEVICE INFO
• Relay type (Type ALLEN BRADLEY 865)
• Serial number (SerN)
• Software version (PrgVer)
• Bootcode version (BootVer)
DATE/TIME SETUP
• Day, month and year (Date)
• Time of day (Time)
• Date format (Style). The choices are "yyyy-mm-dd",
"dd.nn.yyyy" and "mm/dd/yyyy".
CLOCK SYNCHRONISATION
• Digital input for minute sync pulse (SyncDI). If any digital input
is not used for synchronization, select "".
• Daylight saving time for NTP synchronization (DST).
• Detected source of synchronization (SyScr).
• Synchronization message counter (MsgCnt).
• Latest synchronization deviation (Dev).
The following parameters are visible only when the access level is
higher than "User".
• Offset, i.e. constant error, of the synchronization source (SyOS).
• Auto adjust interval (AAIntv).
• Average drift direction (AvDrft): "Lead" or "lag".
• Average synchronization deviation (FilDev).
Configuration and
Parameter Setting
(