Manual
Local Panel User Interface 2-23
865-UM001A-EN-P – July 2009
Disturbance Recorder Menu DR
Via the submenus of the disturbance recorder menu the
following functions and features can be read and set:
DISTURBANCE RECORDER
• Recording mode (Mode)
• Sample rate (Rate)
• Recording time (Time)
• Pre trig time (PreTrig)
• Manual trigger (MnlTrig)
• Count of ready records (ReadyRe)
REC. COUPLING
• Add a link to the recorder (AddLink)
• Clear all links (ClrLnks)
Available links:
• DO, DI
• IL, I’L
• I2/In, I2/I1, I2, I1, IoCalc, I2/In, I’2/I’1, I’2, I’1, I’oCalc
• f
• Io2, Io1
• IL3, IL2, IL1, I’L3, I’L2, I’L1
• IL1RMS, IL2RMS, IL3RMS
• ILmin, ILmax, I’Lmin, I’Lmax
• ΔIl1, ΔIl2, ΔIl3
• IL1w, IL2w, IL3w, I’L1w, I’L2w, I’L3w
Configuring Digital Inputs DI
The following functions can be read and set via the submenus of
the digital inputs menu:
• The status of digital inputs (DIGITAL INPUTS 1-6)
• Operation counters (DI COUNTERS)
• Operation delay (DELAYs for DigIn)
• The polarity of the input signal (INPUT POLARITY). Either
normally open (NO) or normally closed (NC) circuit.
• Event enabling EVENT MASK1