Manual
7-14 Communications
865-UM001A-EN-P – July 2009
Table 7.11 – DPN 3.0 Parameters
Parameter Value Unit Description Set
bit/s
4800
9600 (default)
19200
38400
bps Communication speed Set
Parity
None (default)
Even
Odd
Parity Set
SlvAddr 1 – 65519 An unique address for the device
within the system
Set
MstrAddr 1 – 65519
255=default
Address of master Set
LLTout 0 – 65535 ms Link layer confirmation timeout Set
LLRetry 1 – 255
1=default
Link layer retry count Set
APLTout 0 – 65535
5000=default
ms Application layer confirmation
timeout
Set
CnfMode
EvOnly (default)
All
Application layer confirmation
mode
Set
DBISup
No (default)
Yes
Double-bit input support Set
SyncMode 0 – 65535 s Clock synchronization request
interval.
0 = only at boot
Set
Set = An editable parameter (password needed)
IEC 60870-5-101
The IEC 60870-5-101 standard is derived from the IEC 60870-5
protocol standard definition. In the Allen-Bradley 865 devices, IEC
60870-5-101 communication protocol is available via menu
selection. The Allen-Bradley unit works as a controlled outstation
(slave) unit in unbalanced mode.
Supported application functions include process data transmission,
event transmission, command transmission, general interrogation,
clock synchronization, transmission of integrated totals, and
acquisition of transmission delay.