Owner's manual

839E Solid-State Flow Sensors User Manual
24 Pub #10000004735 Ver 03, May 2012
Technical data
Power supply
Supply voltage
DC voltage version
18...30 V DC
Current consumption
< 100 mA (open-circuit operation) at 24 V DC, max. 150 mA (open-circuit operation); with
reverse polarity protection
Power supply failure
Behavior in case of overvoltage (> 30V)
The device works continuously up to 34V DC without any damage. No damage is caused to
the device in case of a short-term overvoltage up to 1 kV (as per EN 61000-4-5). If the supply
voltage is exceeded, the properties specified are no longer guaranteed.
Behavior in case of undervoltage
If the supply voltage drops below the minimum value, the device switches off (status as if
not supplied with power = switch open).
Output
Switching capacity
Switch status ON: Ia 250 mA
Switch status OFF: Ia 1 mA
Switching cycles: 10,000,000
Voltage drop PNP: 2 V
Overload protection
Automatic load testing of switching current; output is switched off in case of overcurrent,
the switching current is tested again every 0.5 sec.; max. capacitance load: 14 mF for max.
supply voltage (without resistive load); periodical protective disconnection in event of
overcurrent (f = 2 Hz) and ‘Warning’ display.
Signal on alarm
Switch outputs: in safe state (switch normally open)