User guide

Technical Data
28
7 Technical Data
7. 1 Display Version
7.1.1 Power Supply
Supply voltage
DC voltage version
12...30V DC
Current consumption
Without load < 60 mA, with reverse polarity protection
Power supply failure
Behavior in case of over voltage
The device works continuously without any damage up to 34V DC.
If the supply voltage is exceeded, the properties specified are no longer guaranteed.
Behavior in case of under voltage
If the supply voltage drops below the minimum value, the device switches off (status as if
not supplied with power = switch open).
7.1.2 Output
Switching capacity
•Switch status ON: I
a
250 mA
•Switch status OFF: I
a
1 mA
Switching cycles: > 10 000 000
Voltage drop PNP: 2V
Overload protection
Automatic load check of switching current; output is switched off in case of over current,
the switching current is tested again every 0.4 sec.; max. capacitance load: 14 μF at max.
supply voltage (without resistive load) max. period length: 0.5 sec.; min. t
on
: 40 μs
Load (analog output)
•Max. (V
supply
6.5V)/0.022 A
Input PLC
Input resistance R
i
2 kΩ
Input current I
i
10 mA
Signal on alarm
•Analog output
3.6 mA / last current value / 21.0 mA adjustable
(if setting 21.0 mA the output is 21.5 mA)
Signal outputs
In safe state (switch normally open)