3-43 Functions
Publication 825-UM001B-EN-P January 2001
Tripping is delayed by 50 ms. This enables the circuit breaker to be actuated rapidly while
preventing unnecessary tripping by current peaks. In the event of a short-circuit, the separate
output relay #1 trips, regardless of the other protective functions. The output relay #1
actuates a circuit breaker with adequate breaking capacity. To prevent the contactor from
opening under short-circuit conditions, relay MR remains blocked at currents 12 I
e
. If a
thermal trip occurred shortly before the short circuit, relay MR assumes the tripped position
as soon as the current has dropped to < 12 I
e
.
Figure 3.25 Interruption of a Short-Circuit
Application
Medium/high-voltage motors
ATTENTION
!
The short-circuit protection function must not be used for switching
off the contactor.
I
Q
1