3-15 Functions
Publication 825-UM001B-EN-P January 2001
Table 3.I Control Functions Summary
➊ Terminals Y11…Y12 must be jumpered.
➋ Minimum waiting time between two warm starts.
Functions
Factory
Setting
Setting
Range
Factory
Setting
Trippi ng
Delay
Range
Factory
Setting
Relays
Selection
Factory
Setting
Bulletin 825-M… Basic Unit
Warm start (% of “cold”
trip)
Off 50…100% 70% 4…60 min. ➋
60 min.
➋
——
Emergency override of
thermal trip ➊
—— — — ———
Bulletin 825-MST Option Card
Analog output assigned
to:
thermal utilization
PT100 max.
temperature
Motor
On
4…20 mA
0…100%
50…200 °C
0…200%
e
—————
Bulletin 825-MST Option Card, Control Input #1: (24V AC/DC; 8 mA)
One of 3 functions can be selected:
1) Pickup delay, relay #2 Off — — 0…240 s 1 s — #2
1) Dropout delay, relay #2 — — — 0…240 s 2 s — #2
2) Speed switch Off — — — — —
high over-
load relay
3) Disable protective functions:
Asymmetry/phase failure Off — — — — — —
High overload/jam Off — — — — — —
Earth (ground) fault Off — — — — — —
Short-circuit Off — — — — — —
Underload Off — — — — — —
Limiting starts/hour Off — — — — — —
PTC Off — — — — — —
PT100 (RTD) Off — — — — — —