2-12 Equipment Description
Publication 825-UM001B-EN-P January 2001
Response Supply Voltage Failure
If the supply voltage fails, the setting data are retained.
Failure of Supply Voltage > 30 ms
All energized output relays drop out
The LED extinguishes
The timer for “duration of supply failure” starts (maximum 8 h)
The instantaneous set and statistical data are recorded
The LCD extinguishes
Recovery of the Supply Voltage
Initialization routine is started
The time of occurrence and the duration of the supply failure are entered into
memory
The thermal image is calculated and updated
All output relays return to the state before the supply failure, except for relay #2 and
#3, when control is executed via communication
LCD and LED activate