User Manual Manual

5-9 Setting the Operational Parameters
Publication 825-UM001B-EN-P January 2001
Table 5.D Cat. No. 825-M Operating Parameters (Continued)
If Warm Starting is set to off, the programming menu skips to parameter Start Inhibit.
If Start Inhibit is set to off, the programming menu skips to parameter Start Control.
If Start Control is set to off, the programming menu skips to parameter Main Relay.
Group
Required
Option Card
Cat. No.
LCD
Setting
Range
Description
Warm start
On/Off
Warm start
On/Off
460
Warm start possible every
___min.
50100
Warm start tripping time as
a percentage of tripping
time from cold
Limiting number of
starts per hour
On/Off
Limiting number of
starts/hour
On/Off
110 Maximum starts/hour
All relays
Maximum number of
starts/hour reached
Assignment of output relay
Monitoring startup
time
On/Off
Monitoring starting time
On/Off
1240 Maximum starting time
All relays
Starting time exceeded
Assignment of output relay
WARM STARTING
OFF
WARM START EACH
60 min
WARM TRIP TIME
70 %
START INHIBIT
OFF
MAX START/HOUR
2
START INHIB TRIP
MAIN RELAY
START CONTROL
OFF
START TIME
10 sec
START CONT TRIP
MAIN RELAY