User Manual Manual

Setting the Operational Parameters 5-8
Publication 825-UM001B-EN-P January 2001
Table 5.D Cat. No. 825-M Operating Parameters (Continued)
If Underload Trip is set to off, the programming menu skips to parameter UL Warning.
If UL Warning is set to off, the programming menu skips to parameter Star Delta.
If Star Delta is set to off, the programming menu skips to parameter Warm Starting.
If Set Star Time is set to off, the programming menu skips to parameter Warm Starting.
Group
Required
Option Card
Cat. No.
LCD
Setting
Range
Description
Underload
On/Off
Underload protection
On/Off
25100
Underload trip
Tripping level%
e
160
Underload trip
Tripping delay
All relays
Underload trip
Assignment of output relay
0240
Underload trip
Start delay
On/Off
Underload warning
On/Off
All except
main relay
Underload warning,
assignment of output relay
(warning level is equal to
tripping level, without
tripping delay)
Star-Delta
(Wye-Delta)
starting
825-MLV
On/Off
Star-delta starting
On/Off
Relay#4
Star-delta starting
Assignment of star output
relay
Relay#5
Star-delta starting
Assignment of delta output
relay
On/Off
Star-delta starting
Max. time on star on/off
1240
Star-delta starting
Max. time on star
UNDERLOAD TRIP
OFF
UL TRIP LEVEL
75 % Ie
UL TRIP TIME
10 sec
UNDERLOAD TRIP
MAIN RELAY
UL START-DELAY
0 sec
UL WARNING
OFF
UL WARNING
ALARM RELAY
STAR DELTA
OFF
STAR AUX REL #4
DELTA AUX REL #5
SET STAR TIME
OFF
STAR TIME
10 sec