Setting the Operational Parameters 5-6
Publication 825-UM001B-EN-P January 2001
Table 5.D Cat. No. 825-M Operating Parameters (Continued)
If Earth Fault Prot is set to off, the programming menu skips to parameter Short Circ Trip.
If EF Holmg Trip is set to off, the programming menu skips to parameter EF CoreTrip.
ATTENTION
!
Ensure that the trip function is reset before it is inactivated.
Group
Required
Option Card
Cat. No.
LCD
Setting
Range
Description
Overcurrent,
continued
1.06.0
Overcurrent/locked-rotor
Warning level in
e
All except
main relay
Overcurrent/locked-rotor
warning
Assignment of output relay
Earth (ground) fault
(Holmgreen/
residual)
On/Off
Earth (ground) fault
protection
On/Off
On/Off
Earth (ground) fault
protection (Holmgreen =
residual) On/Off
10100
Earth (ground) fault trip
(Holmgreen = residual
Tripping level, percent of
motor current
0.15
Earth (ground) fault trip
(Holmgreen = residual)
Tripping delay
All relays
Earth (ground) fault trip
(Holmgreen = residual)
Assignment of output relay
OC WARNING LEVEL
2.0 x Ie
OC WARNING
ALARM RELAY
EARTH FAULT PROT
ON
EF HOLMG TRIP
ON
EF H TRIP LEVEL
50 %
EF H TRIP TIME
0.50 sec
EF HOLMG TRIP
MAIN RELAY