5-5 Setting the Operational Parameters
Publication 825-UM001B-EN-P January 2001
Table 5.D Cat. No. 825-M Operating Parameters (Continued)
If Asymmetry Trip is set to off, the programming menu skips to parameter AS Warning.
If AS Warning is set to off, the programming menu skips to parameter Overcurr Trip.
If OC Warning is set to off, the programming menu skips to parameter Earth Fault Prot.
Group
Required
Option Card
Cat. No.
LCD
Setting
Range
Description
Asymmetry
On/Off
Asymmetry protection
(current measuring
asymmetry) On/Off
580
Asymmetry trip
Tripping level in percent
125
Asymmetry trip
Tripping delay
All relays
Asymmetry trip
Assignment of relays
On/Off
Asymmetry warning
On/Off
580
Asymmetry warning
Warning level in percent
All except
main relay
Asymmetry warning
Assignment of output relay
Overcurrent
On/Off
Overcurrent/locked-rotor
protection On/Off
1.06.0
Overcurrent/locked-rotor
Tripping level in
e
0.15
Overcurrent/locked-rotor
Tripping delay
All relays
Overcurrent/locked-rotor
Assignment of output relay
On/Off
Overcurrent/locked-rotor
warning On/Off
ASYMMETRY TRIP
ON
AS TRIP LEVEL
35 %
AS TRIP TIME
2.5 sec
ASYMMETRY TRIP
MAIN RELAY
AS WARNING
OFF
AS WARNING LEVEL
20 %
AS WARNING
ALARM RELAY
OVERCURR TRIP
ON
OC TRIP LEVEL
2.4
X Ie
OC TRIP TIME
0.5 sec
OVERCURRENT TRIP
MAIN RELAY
OC WARNING
OFF