User Manual User Manual
Publication 825-UM002A-EN-P - December 2000
A-43
ODVA Drive Profile Fault and Warning Codes Supported,
Continued
ODVA Fault
Code (hex)
ODVA Fault
Indication
SMM
LCD Indication
Possible Causes Corrective Action
49 hex Trips/Hour Exceeded START INHIB TRIP 1. Wait until a further start is permissible.
Release will be automatic
65 hex Tripping Time Exceeded START CONTR TRIP 1. Overloaded
2. Transport material jammed
3. Viscous material
1. Reduce load or raise max. starting time
2. Eliminate cause
3. Raise max. starting time
66 hex Transducer MCM NOT CONNECT
FAULT MCM
1. Cable SMM <-> MCM broken or
not connected
2. Fault in 825-SMM or 825-MCM
1. Check connections, test cable
2. Send 825-SMM or 825-MCM back for
repair
2250 hex Short Circuit SHORT CIRC PROT 1. Short circuit or earth fault in
motor or cable
2. Trip when motor switched on,
due to inrush current
3. Pickup threshold is < Ia
1. Repair damage
2. Increase trip delay to >0.1 s
3. Set pickup threshold to > Ia
4310 hex Excess Motor
Temperature
PT100 #...WARNING
PT100 #...TRIP
PTC TRIP
1. Stator winding overheated
2. PT100/PT100 leads or PTC/PTC
leads shorted or broken
1. Wait for motor to cool
2. Check leads or switch off PTC
monitoring
8114 hex Illegal FLC Setting IE OUT OF RANGE 1. Rated current MCM does not
agree with SMM setting
2. Wrong MCM
3. Wrong setting
1. Check setting of “FULL LOAD CURR”
and MCM
2. Install a correct MCM
3. Change FULL LOAD CURR setting
8116 hex Command Outside
Window
ERROR ACTUAL VAL