Instance Attributes, Continued
Available with SMM version 3.11 (or higher) / 825-MDN version 6.001 (or higher) product combination only.
Available with SMM version 2.xx (and lower).
Attribute
ID
Access
Rule
Name (param. #) Data
Ty pe
Min/Max Units Default Description
136 Get/Set warm_st_ (#70) BOOL 01 0=OFF 0 Warm start, on/off
137 Get/Set warm_tim (#71) USINT 460 minutes 60 Warm start allowed every minutes
138 Get/Set wa_trip_ (#72) USINT 50100 % 70 Warm start tip time,% trip time from cold
139 Get/Set start_in (#73) BOOL 01 0=OFF 0 Limiting the number of starts/h, on/off
140 Get/Set start/h_ (#74) USINT 110 starts/hr 2 Maximum starts/h
141 Get/Set st_contr (#76) BOOL 01 0=OFF 0 Monitoring start time (start inhibit) on/off
142 Get/Set st_time_ (#77) USINT 1240 seconds 10 Maximum starting time
143 Get/Set autrs_th (#80) BOOL 01 0=man. 0 Thermal trip reset, automatic/manual
144 Get/Set th_res_l (#81) USINT 10100 % 50 Thermal trip reset at % of therm.
utilize.
145 Get/Set cool_rat (#82) USINT 1050 0.1 25 Cooling constant ratio, motor off/on
(1.05.0)
146 Get/Set dis_ass1 (#93) BOOL 01 1=disabl 0 Asymmetry protection, enabled/disabled
147 Get/Set dis_ol_1 (#94) BOOL 01 1=disabl 0 Overcurrent/locked rotor protection,
enabled/disabled
148 Get/Set dis_ess1 (#95) BOOL 01 1=disabl 0 Earth fault protection, enabled/disabled
149 Get/Set dis_kss1 (#96) BOOL 01 1=disabl 0 Short circuit protection, enabled/disabled
150 Get/Set dis_uls1 (#97) BOOL 01 1=disabl 0 Underload protection, enabled/disabled
151 Get/Set dis_sti1 (#98) BOOL 01 1=disabl 0 Limiting the starts per hour, enabled/
disabled
152 Get/Set new_flc_ (#105) BOOL 010=OFF0
2
nd
rated motor current, on/off
153
Get/Set new_Ie__ (#106) UDINT 50200,000 10 mA 2000
2
nd
rated motor current, value
(0.502000.00 A)
153
Get/Set new_Ie__ (#106) UINT 5063,000 10 mA 2000
2
nd
rated motor current, value
(0.50630.00 A)
154 Get/Set dis_ass2 (#108) BOOL 01 1=disabl 0 Asymmetry protection, enabled/disabled
155 Get/Set dis_ol_2 (#109) BOOL 01 1=disabl 0 Overcurrent/locked rotor protection,
enabled/disabled
156 Get/Set dis_ess2 (#110) BOOL 01 1=disabl 0 Earth fault protection, enabled/disabled
157 Get/Set dis_kss2 (#111) BOOL 01 1=disabl 0 Short circuit protection, enabled/disabled
158 Get/Set dis_uls2 (#112) BOOL 01 1=disabl 0 Underload protection, enabled/disabled
159 Get/Set dis_sti2 (#113) BOOL 01 1=disabl 0 Limiting the starts per hour, enabled/
disabled