User Manual User Manual
Publication 825-UM002A-EN-P - December 2000
A-37
Instance Attributes
➊ Bit definitions given on page A-40.
➋ Available with SMM version 3.11 (or higher) / 825-MDN version 6.001 (or higher) product combination.
➌ Available with SMM version 2.xx ( and lower).
Attribute
ID
Access
Rule
Name (param. #) Data
Ty pe
Min/Max Units Default Description
1 Get numAttr USINT Number of Attributes supported
2 Get Attributes Array
USINT
List of attributes supported by the
Overload
3
➋
Set/Get le________ (#21) UDINT 30…200,000 10 mA 2000 FLC Setting Value
3
➌
Set/Get le________ (#21) UINT 50…63,000 10 mA 2000 FLC Setting Value
165 Set/Get t_block_ (#23) UINT 1…600 seconds 10 Max Stall Time
5 Get lmotor__ (#1)) INT 0…1200 % FLC 0 Average Motor Current
6 Get Asymetry (#7) USINT 0…100 % 0 % Asymmetry
7 Get Th.Util_ (#2) USINT 0…100 % 0 % Thermal Utilization
8 Get lmot__L1 (#3) INT 0…1200 % FLC 0 I phase L1
9 Get lmot__L2 (#4) INT 0…1200 % FLC 0 I phase L2
10 Get lmot__L3 (#5) INT 0…1200 % FLC 0 I phase L3
11 Get learth_S (#9) UINT 0…55000 .005 Amps 0 Earth Core
102 Get Time_to_ (#6) UINT 1…9999 seconds 9999 Time to Trip/Reset
103 Get Iearth_H (#8) USINT 0…100 % 0 Earth-fault current (Holmgreen)
104
➊
Get iAUSL___ (#18) WORD 0…0xffff bits 0 Actual Trip Bit String (Bit Pattern)
105
➊
Get iVORW___ (#19) WORD 0…0xffff bits 0 Actual Warning Bit String (Bit Pattern)
106 Get/Set Ibl/Ie__ (#22) USINT 25…120 times
0.1*FLC
60 Locked rotor current (2.5…12.0 times FLC)
107 Get/Set th_alarm (#25) BOOL 0…1 0=OFF 0 Thermal warning, on/off
108 Get/Set th_al_le (#26) USINT 50…99 % 75 Thermal warning level