User Manual User Manual

Publication 825-UM002A-EN-P - December 2000
A-35
Specific Instance Attributes, Continued
Available with SMM version 3.11 (or higher) / 825-MDN version 6.001 (or higher) product combination only.
Attribute ID Access
Rule
Name
(param. #)
Data
Ty pe
Min/
Max
Default Description
131 Get/Set sp2_t_of (#104) USINT 0240 2 Off-delay of auxiliary relay #3
132 Get/Set dis_fct2 (#107) BOOL 01 0 Disable protection functions from Control Input #2 on/off
133 Get/Set drs_tr_r (#117) USINT 07 0 Phase reversal trip, relay assignment
134 Get/Set pas_tr_r (#119) USINT 07 0 Phase loss trip, relay assignment
135 Get/Set pt_tr_re (#133) USINT 04, 7 0 Pt100 #1#6 trip, relay assignment
136 Get/Set pt_al_re (#148) USINT 14, 7 1 Pt100 #1#6 warning, relay assignment
137
Get sp_in_st (#20) UINT 03 0 Status of Control inputs #1 and #2; bit 0=Input 1 status,
bit 8=Input 2 status; 0=OFF, 1=ON
138
Get/Set re2_comm (#225) BOOL 01 0 Aux #2 relay ON/OFF command
139
Get/Set re3_comm (#226) BOOL 01 0 Aux #3 relay ON/OFF command
140
Get/Set anout_us (#230) USINT 02 0 Analog output configuration:
0=Thermal utilization (0-100%)
1=PT100max (0-200°C)
2=Motor current (0-200%)
141
Get/Set rel_remt (#231) BOOL 01 0 Control relays #2 and #3 via DeviceNet
142 Get/Set Aux2 Pr FltState (#234) BOOL 01 0 Aux relay #2 behavior on a trip condition.
0 = Go to Value, 1= Hold Last State
143 Get/Set Aux2 Pr FltValue (#235) BOOL 01 0 Go To Value setting for parameter #234.
0 = OFF, 1= On
144 Get/Set Aux2 Dn FltState (#236) BOOL 01 0 Aux relay #2 behavior on a comm. fault condition. 0 =
Go to Value, 1= Hold Last State
145 Get/Set Aux2 Dn FltValue (#237) BOOL 01 0 Go To Value setting for parameter #236.
0 = OFF, 1= On
146 Get/Set Aux2 Dn IdlState (#238) BOOL 01 0 Aux relay #2 behavior on a comm. idle condition. 0 = Go
to Value, 1= Hold Last State
147 Get/Set Aux2 Dn IdlValue (#239) BOOL 01 0 Go To Value setting for parameter #238.
0 = OFF, 1= On
148 Get/Set Aux3 Pr FltState (#240) BOOL 01 0 Aux relay #3 behavior on a trip condition.
0 = Go to Value, 1= Hold Last State
149 Get/Set Aux3 Pr FltValue (#241) BOOL 01 0 Go To Value setting for parameter #240.
0 = OFF, 1= On
150 Get/Set Aux3 Dn FltState (#242) BOOL 01 0 Aux relay #3 behavior on a comm. fault condition. 0 =
Go to Value, 1= Hold Last State
151 Get/Set Aux3 Dn FltValue (#243) BOOL 01 0 Go To Value setting for parameter #242. 0 = OFF, 1= On
152 Get/Set Aux3 Dn IdlState (#244) BOOL 01 0 Aux relay #3 behavior on a comm. idle condition. 0 = Go
to Value, 1= Hold Last State
153 Get/Set Aux3 Dn IdlValue (#245) BOOL 01 0 Go To Value setting for parameter #244. 0 = OFF, 1= On