Specific Instance Attributes
➊ Available with SMM version 3.11 (or higher) / 825-MDN version 6.001 (or higher) product combination only.
Attribute ID Access
Rule
Name
(param. #)
Data
Typ e
Min/
Max
Default Description
100 Get/Set rel_th_t (#24) USINT 0, 7 0 Thermal trip, relay assignment
101 Get/Set th_al_re (#27) USINT 1…7 1 Thermal warning, relay assignment
102 Get/Set as_tr_re (#31) USINT 0…7 0 Asymmetry trip, relay assignment
103 Get/Set as_al_re (#34) USINT 1…7 1 Asymmetry warning, relay assignment
104 Get/Set ol_tr_re (#38) USINT 0…7 0 Overcurrent/locked rotor, trip relay
105 Get/Set ol_al_re (#41) USINT 1…7 1 Overcurrent/locked rotor, warning relay assignment
106 Get/Set efh_tr_r (#46) USINT 0…7 0 Earth-fault (Holmgreen), trip relay
107 Get/Set efs_tr_r (#50) USINT 0…7 0 Earth-fault (Core balance), trip relay assignment
108 Get/Set efs_al_r (#53) USINT 1…7 1 Earth-fault (Core balance), warning relay assignment
109 Get/Set sc_tr_re (#57) USINT 2, 7 2 Short circuit, trip relay assignment
110 Get/Set ul_tr_re (#61) USINT 0…7 0 Underload, trip relay assignment
111 Get/Set ul_al_re (#64) USINT 1…7 1 Underload, warning relay assignment
112 Get/Set star/del (#65) BOOL 0…1 0 Star-delta starting, on/off
113 Get st_relai (#66) USINT 5 5 Star-delta starting, star relay
114 Get delta_re (#67) USINT 6 6 Star-delta starting, delta relay
115 Get/Set star_tim (#68) BOOL 0…1 0 Star-delta starting, max. star time on/off
116 Get/Set star_tmx (#69) USINT 1…240 10 Star-delta starting, max. star time
117 Get/Set st/h_rel (#75) USINT 0…7 0 Maximum starts/h, relay assignment
118 Get/Set st_ti_re (#78) USINT 0…7 0 Starting time exceeded, relay assignment
119 Get/Set arb/ruhe (#79) BOOL 0…1 0 Main relay and warning relay connection: non-failsafe
(0), electrically held (1)
120 Get/Set ptc_tr_r (#84) USINT 0, 7 0 PTC trip, relay assignment
121 Get/Set sp_in_#1 (#86) BOOL 0…1 0 Control Input #1, on/off
122 Get/Set spin1_tr (#87) BOOL 0…1 0 Time delay of aux. Relay #2, on/off
123 Get/Set sp1_t_on (#88) USINT 0…240 1 On-delay of auxiliary relay #2
124 Get/Set sp1_t_of (#89) USINT 0…240 2 Off-delay of auxiliary relay #2
125 Get/Set speed_sw (#90) BOOL 0…1 0 Speed switch/stop indicator on/off
126 Get/Set sp_sw_re (#91) USINT 0…7 0 Speed switch/stop indicator, trip relay
127 Get/Set dis_fct1 (#92) BOOL 0…1 0 Disable protection functions from Control Input #1 on/off
128 Get/Set sp_in_#2 (#101) BOOL 0…1 0 Control Input #2, on/off
129 Get/Set spin2_tr (#102) BOOL 0…1 0 Time delay of aux. Relay #3, on/off
130 Get/Set sp2_t_on (#103) USINT 0…240 1 On-delay of auxiliary relay #3