User Manual User Manual

Publication 825-UM002A-EN-P - December 2000
A-24
Parameters Supported, Continued
Parameter
No.
®=read-only
Parameter Name Object
Mapping
Description Data
Typ e
Units Min/
Max
Default
232
®
Sp Sw Trip Delay 0x2C-1-171 Speed Switch Trip Delay USINT 0.1 s 150 5
233
®
SMM Revision 0xB4-1-12 SMM/CET4 firmware revision UINT
234
Aux2 Pr FltState 0x29-1-142 Aux relay #2 behavior on a trip condition.
0 = Go to Value, 1= Hold Last State
BOOL 010
235
Aux2 Pr FltValue 0x29-1-143 Go To Value setting for parameter #234.
0 = OFF, 1= On
BOOL 010
236
Aux2 Dn FltState 0x29-1-144 Aux relay #2 behavior on a comm. fault
condition. 0 = Go to Value, 1= Hold Last
State
BOOL 010
237
Aux2 Dn FltValue 0x29-1-145 Go To Value setting for parameter #236.
0 = OFF, 1= On
BOOL 010
238
Aux2 Dn IdlState 0x29-1-146 Aux relay #2 behavior on a comm. idle
condition. 0 = Go to Value, 1= Hold Last
State
BOOL 010
239
Aux2 Dn IdlValue 0x29-1-147 Go To Value setting for parameter #238.
0 = OFF, 1= On
BOOL 010
240
Aux3 Pr FltState 0x29-1-148 Aux relay #3 behavior on a trip condition.
0 = Go to Value, 1= Hold Last State
BOOL 010
241
Aux3 Pr FltValue 0x29-1-149 Go To Value setting for parameter #240.
0 = OFF, 1= On
BOOL 010
242
Aux3 Dn FltState 0x29-1-150 Aux relay #3 behavior on a comm. fault
condition. 0 = Go to Value, 1= Hold Last
State
BOOL 010
243
Aux3 Dn FltValue 0x29-1-151 Go To Value setting for parameter #242.
0 = OFF, 1= On
BOOL 010
244
Aux3 Dn IdlState 0x29-1-146 Aux relay #3 behavior on a comm. idle
condition. 0 = Go to Value, 1= Hold Last
State
BOOL 010
245
Aux3 Dn IdlValue 0x29-1-153 Go To Value setting for parameter #244.
0 = OFF, 1= On
BOOL 010