User Manual User Manual
Publication 825-UM002A-EN-P - December 2000
A-24
Parameters Supported, Continued
Parameter
No.
®=read-only
Parameter Name Object
Mapping
Description Data
Typ e
Units Min/
Max
Default
232
®➊
Sp Sw Trip Delay 0x2C-1-171 Speed Switch Trip Delay USINT 0.1 s 1…50 5
233
®➊
SMM Revision 0xB4-1-12 SMM/CET4 firmware revision UINT
234
➊
Aux2 Pr FltState 0x29-1-142 Aux relay #2 behavior on a trip condition.
0 = “Go to Value”, 1= “Hold Last State”
BOOL 0…10
235
➊
Aux2 Pr FltValue 0x29-1-143 Go To Value setting for parameter #234.
0 = OFF, 1= On
BOOL 0…10
236
➊
Aux2 Dn FltState 0x29-1-144 Aux relay #2 behavior on a comm. fault
condition. 0 = “Go to Value”, 1= “Hold Last
State”
BOOL 0…10
237
➊
Aux2 Dn FltValue 0x29-1-145 Go To Value setting for parameter #236.
0 = OFF, 1= On
BOOL 0…10
238
➊
Aux2 Dn IdlState 0x29-1-146 Aux relay #2 behavior on a comm. idle
condition. 0 = “Go to Value”, 1= “Hold Last
State”
BOOL 0…10
239
➊
Aux2 Dn IdlValue 0x29-1-147 Go To Value setting for parameter #238.
0 = OFF, 1= On
BOOL 0…10
240
➊
Aux3 Pr FltState 0x29-1-148 Aux relay #3 behavior on a trip condition.
0 = “Go to Value”, 1= “Hold Last State”
BOOL 0…10
241
➊
Aux3 Pr FltValue 0x29-1-149 Go To Value setting for parameter #240.
0 = OFF, 1= On
BOOL 0…10
242
➊
Aux3 Dn FltState 0x29-1-150 Aux relay #3 behavior on a comm. fault
condition. 0 = “Go to Value”, 1= “Hold Last
State”
BOOL 0…10
243
➊
Aux3 Dn FltValue 0x29-1-151 Go To Value setting for parameter #242.
0 = OFF, 1= On
BOOL 0…10
244
➊
Aux3 Dn IdlState 0x29-1-146 Aux relay #3 behavior on a comm. idle
condition. 0 = “Go to Value”, 1= “Hold Last
State”
BOOL 0…10
245
➊
Aux3 Dn IdlValue 0x29-1-153 Go To Value setting for parameter #244.
0 = OFF, 1= On
BOOL 0…10