User Manual User Manual
Publication 825-UM002A-EN-P - December 2000
A-23
Parameters Supported, Continued
➊ Available with SMM version 3.11 (or higher) / 825-MDN version 6.001 (or higher) product combination only.
Parameter
No.
®=read-only
Parameter Name Object
Mapping
Description Data
Typ e
Units Min/
Max
Defaul
t
217 Assembly Word 0 0xB4-1-7 Used when Param #216 = 100 USINT 0…214 1
218 Assembly Word 1 0xB4-1-8 Used when Param #216 = 100 USINT 0…214 0
219 Assembly Word 2 0xB4-1-9 Used when Param #216 = 100 USINT 0…214 0
220 Assembly Word 3 0xB4-1-10 Used when Param #216 = 100 USINT 0…214 0
221
®
Hdw. Installed 0x0F-221-1 Option Cards Installed bit-string
bit0 - 825-MST
bit1 - not used
bit2 - 825-MLV
bit3 - 825-MMV
bit4 - 825-MDN (DeviceNet)
WORD 0…31
222
®
Current Convert. 0x0F-222-1 Current Converter bit-string
bit0 - 2.5 A
bit1 - 20 A
bit2 - 180 A
bit3 - 630 A
WORD 1…8
223 Default DN IO 0xB4-1-21 Sets parameters 215…220 to their
factory defaults.
0=no action, 1=reset to defaults
WORD 0…10
224
®➊
TH Bef Last Trip 0x0F-224-1 Thermal Utilization Before Last Trip UINT % 0…100 0
225
➊
Aux #2 Cmd 0x29-1-138 Turns Aux #2 relay ON or OFF when
p231 is enabled. 0=OFF, 1=ON, 2=no
comm control
USINT 0…20
226
➊
Aux #3 Cmd 0x29-1-139 Turns Aux #3 relay ON or OFF when
p231 is enabled. 0=OFF, 1=ON, 2=no
comm control
USINT 0…20
227
➊
2nd Prim CT Used 0x2C-1-168 Second primary CT enable BOOL 0…10
228
➊
2nd Prim CT Rat 0x2C-1-169 Second primary-to-secondary CT ratio UINT 1…2000 1
229
➊
Core CT Ratio 0x2C-1-170 Core balance CT
primary-to-secondary ratio
UINT 1…2000 100
230
➊
Analog Out Cfg 0x29-1-140 0=Thermal Utilization (0…100%)
1=PT100max (0…200
°
C)
2=Motor current (0…200%)
USINT 0…20
231
➊
Aux Relay
Remote
0x29-1-141 Control relays Aux #2 and #3 via
DeviceNet
BOOL 0…10