User Manual User Manual

Publication 825-UM002A-EN-P - December 2000
A-20
Parameters Supported, Continued
Parameter
No.
®=read-only
Parameter
Name
Object
Mapping
Description Data
Typ e
Units Min/Max Default
123 PT100 #2 Trip 0x0F-123-1 PT100 #2 Trip, 0=OFF 1=ON BOOL 010
124 #2 Trip Temp 0x0F-124-1 PT100 #2 Trip, Temperature USINT
°
C 50200 50
125 PT100 #3 Trip 0xB4-1-19 PT100 #3 Trip, 0=OFF 1=ON BOOL 010
126 #3 Trip Temp 0x0F-126-1 PT100 #3 Trip, Temperature USINT
°
C 50200 50
127 PT100 #4 Trip 0x0F-127-1 PT100 #4 Trip, 0=OFF 1=ON BOOL 010
128 #4 Trip Temp 0x0F-128-1 PT100 #4 Trip, Temperature USINT
°
C 50200 50
129 PT100 #5 Trip 0x0F-129-1 PT100 #5 Trip, 0=OFF 1=ON BOOL 010
130 #5 Trip Temp 0x0F-130-1 PT100 #5 Trip, Temperature USINT
°
C 50200 50
131 PT100 #6 Trip 0x0F-131-1 PT100 #6 Trip, 0=OFF 1=ON BOOL 010
132 #6 Trip Temp 0x0F-132-1 PT100 #6 Trip, Temperature USINT
°
C 50200 50
133 PT100 #1-6 Relay 0x29-1-135 PT100 #1...#6 Trip, Relay Assignment USINT 04, 7 0
134 PT100 #1-6 Reset 0x0F-134-1 PT100 #1...#6 Trip Reset, 0=Manual
1=Automatic
BOOL 010
136 #1 Warning 0x0F-136-1 PT100 #1 Warning, 0=Off 1=On BOOL 010
137 #1 Warning Temp 0x0F-137-1 PT100 #1 Warning, temperature USINT
°
C 50200 50
138 #2 Warning 0x0F-138-1 PT100 #2 Warning, 0=Off 1=On BOOL 010
139 #2 Warning Temp 0x0F-139-1 PT100 #2 Warning, temperature USINT
°
C 50200 50
140 #3 Warning 0x0F-140-1 PT100 #3 Warning, 0=Off 1=On BOOL 010
141 #3 Warning Temp 0x0F-141-1 PT100 #3 Warning, temperature USINT
°
C 50200 50
142 #4 Warning 0x0F-142-1 PT100 #4 Warning, 0=Off 1=On BOOL 010
143 #4 Warning Temp 0x0F-143-1 PT100 #4 Warning Temperature USINT
°
C 50200 50
144 #5 Warning 0x0F-144-1 PT100 #5 Warning, 0=Off 1=On BOOL 010
145 #5 Warning Temp 0x0F-145-1 PT100 #5 Warning, temperature USINT
°
C 50200 50
146 #6 Warning 0x0F-146-1 PT100 #6 Warning, 0=Off 1=On BOOL 010
147 #6 Warning Temp 0x0F-147-1 PT100 #6 Warning, temperature USINT
°
C 50200 50
148 #1-6 Warning Rel 0x29-1-136 PT100 #1-#6 Warning Relay 1=alarm
2=Aux #1 3=Aux #2 4=Aux #3
7=None
USINT 14, 7 1
150 T amb in Image 0x0F-150-1 PT100 #7 Include Ambient Temperature
in Thermal Image, 0=OFF 1=ON
BOOL 010
151 ® Device MAC ID 0x03-1-1 Device MAC ID USINT 063 63
152 ® Baud Rate 0x03-1-2 Communication Baud Rate 0=125kB
1=250kB 2=500kB
USINT 020
154 Trip Reset 0x29-1-12 Remote Trip Reset Via Communications
0=No Reset 1=Reset
BOOL 010