Parameters Supported, Continued
Available with SMM version 3.11 (or higher) / 825-MDN version 6.001 (or higher) product combination.
Available with SMM version 2.xx (and lower).
Parameter
No.
®=read-only
Parameter Name Object
Mapping
Description Data
Typ e
Units Min/Max Default
100 PT100 Prot #1 0x0F-100-1 PT100 Protection, 0=Not Disable
1=Disable
BOOL 010
101 Control Input #2 0x29-1-128 Control Input #2, 0=OFF 1=ON BOOL 010
102 Delay Aux Rel #3 0x29-1-129 Time Delay of Auxiliary Relay #3, 0=OFF
1=ON
BOOL 010
103 On Delay Aux #3 0x29-1-130 ON Delay of Auxiliary Relay #3 USINT seconds 0240 1
104 Off Delay Aux #3 0x29-1-131 OFF Delay of Auxiliary Relay #3 USINT seconds 0240 2
105 2nd FLC Enable 0x2C-1-152 2nd Rated Motor Current, 0=OFF 1=ON BOOL 010
106
2nd FLC 0x2C-1-153 2nd Rated Motor Current, Value
(0.502000.00 A)
UDINT 0.01 A 50200,000 2000
106
2nd FLC 0x2C-1-153 2nd Rated Motor Current, Value
(0.50630.00 A)
UINT 0.01 A 5063,000 2000
107 Disable Prot #2 0x29-1-132 Disable Protective Functions, 0=OFF
1=ON
BOOL 010
108 As Prot #2 0x2C-1-154 Asymmetry Protection, 0=Not Disable
1=Disable
BOOL 010
109 OC Prot #2 0x2C-1-155 Overcurrent / Locked-Rotor Protection,
0=Not Disable 1=Disable
BOOL 010
110 EF Prot #2 0x2C-1-156 Earth Fault Protection, 0=Not Disable
1=Disable
BOOL 010
111 SC Prot #2 0x2C-1-157 Short Circuit Protection, 0=Not Disable
1=Disable
BOOL 010
112 UL Prot #2 0x2C-1-158 Underload Protection, 0=Not Disable
1=Disable
BOOL 010
113 St Inhib Prot #2 0x2C-1-159 Limiting the Starts Per Hour, 0=Not
Disable 1=Disable
BOOL 010
114 PTC Prot #2 0x0F-114-1 PTC Protection, 0=Not Disable
1=Disable
BOOL 010
115 PT100 Prot #2 0x0F-115-1 PT100 Protection, 0=Not Disable
1=Disable
BOOL 010
116 Phase-Rever Trip 0x2C-1-160 Phase Reversal Trip, 0=OFF 1=ON BOOL 010
117 Phase-Rever Rel 0x29-1-133 Phase Reversal Trip Relay Assignment USINT 070
118 Phase Loss Trip 0x2C-1-161 Phase Loss Trip, 0=OFF 1=ON BOOL 010
119 Phase Loss Rel 0x29-1-134 Phase Loss Trip, Relay Assignment USINT 070
120 PT100 Prot 0x0F-120-1 PTC Protection, 0=OFF 1=ON BOOL 010
121 PT100 #1 Trip 0x0F-121-1 PT100 #1 Trip, 0=OFF 1=ON BOOL 010
122 #1 Trip Temp 0x0F-122-1 PT100 #1 Trip, Temperature USINT
°
C 50200 50