User Manual User Manual

Publication 825-UM002A-EN-P - December 2000
A-18
Parameters Supported, Continued
Parameter
No.
®=read-only
Parameter Name Object
Mapping
Description Data
Typ e
Units Min/
Max
Default
77 Max. Start Time 0x2C-1-142 Maximum Starting Time USINT seconds 1240 10
78 Starttime Exceed 0x29-1-118 Starting Time Exceeded, Relay Assignment USINT 070
79 Rel-con Mn/Wrn 0x29-1-119 Main / Warning Relay Connection.
Bit-string
0=Non-Fail-Safe 1=Fail Safe
WORD 0195 128
80 Th Trip Reset 0x29-1-143 Thermal Trip Reset, 0=Manual
1=Automatic
BOOL 010
81 Th Reset Level 0x2C-1-144 Thermal Trip Reset at... % of Thermal
Utilization
USINT % 1010
0
50
82 Cool-Const Ratio 0x2C-1-145 Cooling Constant Ratio, Motor OFF / Motor
ON (1.05.0)
USINT 0.1 1050 25
83 PTC Trip 0x0F-83-1 Thermal Protection PTC, 0=OFF 1=ON BOOL 010
84 PTC Trip Relay 0x29-1-120 PTC Trip, Relay Assignment USINT 070
85 PTC Trip Reset 0x0F-85-1 PTC Trip Reset, 0=Manual, 1=Automatic BOOL 010
86 Control Input #1 0x29-1-121 Control Input #1, 0=OFF 1=ON BOOL 010
87 Delay Aux Rel #2 0x29-1-122 Time Delay of Auxiliary Relay #2, 0=OFF
1=ON
BOOL 010
88 On Delay Aux #2 0x29-1-123 On Delay of Auxiliary Relay #2 USINT seconds 0240 1
89 Off Delay Aux #2 0x29-1-124 Off Delay of Auxiliary Relay #2 USINT seconds 0240 2
90 Speed Switch 0x29-1-125 Speed Switch / Stop Indicator, 0=OFF 1=ON BOOL 010
91 ® Sp Switch Relay 0x29-1-126 Speed Switch / Stop Indicator, Trip Relay
Assignment (is the same as no. 38)
USINT 070
92 Disable Prot #1 0x29-1-127 Disable Protective Functions, 0=OFF
1=ON
BOOL 010
93 As Prot #1 0x2C-1-146 Asymmetry Protection, 0=Not Disable
1=Disable
BOOL 010
94 OC Prot #1 0x2C-1-147 Overcurrent / Locked-Rotor Protection,
0=Not Disable 1=Disable
BOOL 010
95 EF Prot #1 0x2C-1-148 Earth Fault Protection, 0=Not Disable
1=Disable
BOOL 010
96 SC Prot #1 0x2C-1-149 Short Circuit Protection, 0=Not Disable
1=Disable
BOOL 010
97 UL Prot #1 0x2C-1-150 Underload Protection, 0=Not Disable
1=Disable
BOOL 010
98 St Inhib Prot #1 0x2C-1-151 Limiting the Starts Per Hour, 0=Not Disable
1=Disable
BOOL 010
99 PTC Prot #1 0x0F-99-1 PTC Protection, 0=Not Disable 1=Disable BOOL 010