Parameters Supported, Continued
Parameter
No.
Parameter
Name
Object
Mapping
Description Data
Ty pe
Units Min/
Max
Default
27 Th Warning Relay 0x29-1-101 Thermal Warning Relay Assignment USINT 171
28 Asymmetry Trip 0x2C-1-109 Asymmetry Protection, 0=OFF 1=ON BOOL 011
29 As Trip Level 0x2C-1-110 Asymmetry Trip Level USINT % 580 35
30 As Trip Delay 0x2C-1-111 Asymmetry Trip Delay Time USINT 0.1 s 10250 25
31 As Trip Relay 0x29-1-102 Asymmetry Trip Relay Assignment USINT 070
32 As Warning 0x2C-1-112 Asymmetry Warning, 0=OFF 1=ON BOOL 010
33 As Warning Level 0x2C-1-113 Asymmetry Warning Level USINT % 580 20
34 As Warning Relay 0x29-1-103 Asymmetry Warning Relay Assignment USINT 171
35 Overcurrent Trip 0x2C-1-114 Overload/Locked Rotor Protection 0=OFF
1=ON
BOOL 011
36 OC Trip Level 0x2C-1-115 Overload/Locked Rotor Trip Level (1.06.0
times FLC)
USINT times
0.1FLC
1060 24
37 OC Trip Delay 0x2C-1-116 Overload/Locked Rotor Trip Delay Time
(0.15.0 sec)
USINT 0.1 s 150 5
38 OC Trip Relay 0x29-1-104 Overload/Locked Rotor Relay Assignment USINT 070
39 OC Warning 0x2C-1-117 Overload/Locked Rotor Warning, 0 = OFF
1=ON
BOOL 010
40 OC Warning Level 0x2C-1-118 Overload/Locked Rotor Warning Level
(1.06.0 *FLC)
USINT times
0.1FLC
1060 20
41 OC Warning Relay 0x29-1-105 Overload/Locked Rotor Warning Relay
Assignment
USINT 171
42 Earth Fault Prot 0x2C-1-119 Earth Fault Protection, 0=OFF 1=ON BOOL 011
43 EF Holmg Trip 0x2C-1-120 Earth Fault Protection (Holmgreen), 0=OFF
1=ON
BOOL 011
44 EF H Trip Level 0x2C-1-121 Earth Fault Protection (Holmgreen), Trip Level USINT %Current 10100 50
45 EF H Trip Delay 0x2C-1-122 Earth Fault Protection (Holmgreen), Trip
Delay Time
USINT 0.1 s 150 5
46 EF H Trip Relay 0x29-1-106 Earth Fault Protection (Holmgreen), Relay
Assignment
USINT 070
47 EF Core Prot 0x2C-1-123 Earth Fault (core balance) Protection,
0=OFF 1=ON
BOOL 010
48 EF C Trip Level 0x2C-1-124 Earth Fault (core balance) Trip Level UINT mA 550,00
0
1000
49 EF C Trip Delay 0x2C-1-125 Earth Fault (core balance) Trip Delay Time
(0.15.0 s)
USINT 0.1 s 150 5
50 EF C Trip Relay 0x29-1-107 Earth Fault (core balance) Trip Relay
Assignment