User Manual User Manual
Publication 825-UM002A-EN-P - December 2000
A-10
Instance 2 Attributes (Predefined Slave Polled I/O Message)
Attribute
ID
Access
Rule
Name Data
Ty pe
Value
1 Get State USINT 0=nonexistant
1=configuring
3=established
4=timed out
2 Get Instance Type USINT 1= Poll Message
3 Get Transport Class Trigger USINT 0x82 - Server, Transport
Class 2
4 Get Produced Connection ID UINT 10xxxxxx100
xxxxxx=node address
5 Get Consumed Connection ID UINT 10xxxxxx101
xxxxxx=node address
6 Get Initial Comm Characteristics USINT 0x21
7 Get Produced Connection Size UINT 0…8 Size of assembly
instance selected
8 Get Consumed Connection Size UINT 0…1 Size of assembly
instance selected
9 Get/Set Expected Packet Rate UINT Set by Master (00)
12 Get/Set Watchdog Action USINT 0=transition to timed out
1=auto delete
2=auto reset
13 Get Produced Connection Path
Length
UINT 0…6 depending on path
type
14 Get/Set Produced Connection Path Set by Master during
configuration
15 Get Consumed Connection Path
Length
UINT 0…6 depending on path
type
16 Get/Set Consumed Connection Path Set by Master during
configuration