User Manual User Manual

Publication 825-UM002A-EN-P - December 2000
A-6
Instance100 Data (User Configurable Input Assembly)
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Parameter Value (Low byte) pointed to by 0X05-2-102.
1 Parameter Value (High byte) pointed to by 0X05-2-102.
2 Parameter Value (Low byte) pointed to by 0X05-2-103.
3 Parameter Value (High byte) pointed to by 0X05-2-103.
4 Parameter Value (Low byte) pointed to by 0X05-2-104.
5 Parameter Value (High byte) pointed to by 0X05-2-104.
6 Parameter Value (Low byte) pointed to by 0X05-2-105.
7 Parameter Value (High byte) pointed to by 0X05-2-105.
Instance 101: Average Current Overload (Input)
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Reserved Reserved Reserved Reserved Reserved Reserved Warning Faulted
1Reserved
2Average 3Ø Current (Low byte)
3Average 3Ø Current (High byte)
Instance 102: Phase Current Overload (Input)
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Reserved Reserved Reserved Reserved Reserved Reserved Warning Faulted
1 Reserved
2 Current Phase L1 (low byte)
3 Current Phase L1 (high byte)
4 Current Phase L2 (low byte)
5 Current Phase L2 (high byte)
6 Current Phase L3 (low byte)
7 Current Phase L3 (high byte)
Instance 103: Current Overload (Input)
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Reserved Reserved Reserved Reserved Reserved Reserved Warning Faulted
1 % Thermal Capacity Used, TCU
2Average 3Ø Current (Low byte)
3Average 3Ø Current (High byte)
4% Asymmetry