2-30 Drive Installation
7000A-RM001A-EN-P – January 2011 7000 “A” Frame
Power Wiring Selection (cont.) Cable Insulation
The cable insulation requirements for the PowerFlex 7000 “A”
Frame drive are given in the tables below.
A T T E N T I O NA T T E N T I O N
Voltage ratings shown in the following
tables are peak line-to-ground. Some cable
manufacturers rate voltage line-to-line RMS.
Ensure the cable meets the rating specified
in the following tables.
Cable Insulation Requirements for AFE Drives with Separate Isolation Transformer
Cable Insulation Rating (kV)
(Maximum Peak Line-to-Ground)
System Voltage (V, RMS)
Machine Side
2400
4.1 2.2
3000
5.12 2.75
3300
5.63 3.0
4160
7.1 3.8
6000
10.8 5.5
6300
11.4 5.8
6600
11.8 6.0
Cabling from secondary side of Isolation Transformer to input of VFD
Cable Insulation Requirements for “Direct-to-Drive” Technology or Integral
Isolation Transformer
Cable Insulation Rating (kV)
(Maximum Peak Line-to-Ground)
System Voltage (V, RMS)
Line Side Machine Side
2400
2.2 2.2
3000
2.75 2.75
3300
3.0 3.0
4160
3.8 3.8
6000
5.5 5.5
6300
5.8 5.8
6600
6.0 6.0