Manual

5-116 Component Definition and Maintenance
7000A-RM001A-EN-P – January 2011 7000 “A” Frame
9. Repeat above steps until you have assigned the desired parameters to
all the traces from Trace1 to Trace16.
10. Now press F9 [TRIGGER] key. The first letter in the second line on
the screen will toggle between C and S. The letter C stands for
Continuous and S stands for Single shot. Select S for single shot
.
11. Press F2 [CONDITION] key. The cursor will move to the “=” equal
sign. This defines the trigger condition. Press up or down arrow keys
to select + sign as the trigger condition for our example.
12. Press F3 [DATA] key. The cursor moves to the data field. In our
example we will enter 8 and then press Enter key.
13. Press F4 [RATE] key. The cursor moves to the rate field. Here we
will enter 0, which is the fastest sample rate (1 msec/sample) and then
press Enter key.
Setting up Diagnostic
Trending (cont.)