7-10 Troubleshooting
7000-UM150I-EN-P June 2013 7000 “B” Frame
FAULT
MESSAGE
FAULT
CODE
DESCRIPTION
RECOMMENDED ACTIONS
configuration of InputProt2 Class (P444).
for this fault code
Check the 120V signal through the
external device
Check the XIO board inputs and
parameter status bits
Input Xfmr/LR OT
136
The temperature switch in the drive Input
Isolation Transformer or Line Reactor has
detected an over-temperature and opened.
There is a thermal switch in each phase
winding, and they are connected in series.
Verify operating conditions (ambient/
altitude/ current levels/ ventilation and
fans/ cooling oil) and verify that the
Rectifier Transformer/Reactor is within
ratings
Check the 120V signal through the
thermal switch
Verify that it is not a faulty switch
Check the XIO board inputs and
parameter status bits
Determine through elimination whether
there is a faulty switch and replace if
necessary
Inv HeatSink FO
76
While Not Running, the Fiber Optic signal
from the TFB on the Inverter Heatsink,
connected to Channel A fiber optic receiver
RX7 on FOI-M-A is not present. This is only
a fault while not running. If this occurs while
running it will appear as a warning.
Check TFB and FOI board for power
Check the Fiber Optic cables are
properly seated in the transmitters and
receivers
Check the fiber optic cable for kinks,
bends, breaks that could be blocking the
signal
This can occur if the sensor is not
connected to the TFB
Inv Temp Ch B FO
77
Not Normally Used: While Not Running, the
Fiber Optic signal from the optional TFB
connected to Channel B fiber optic receiver
RX7 on FOI-M-B is not present. This is only
a fault while not running. If this occurs while
running it will appear as a warning.
Inv HS Low Temp
40
If the measured temperature IHeatsink
Temp C (P253) is less than 2°C, and the
drive is not running, the drive will display this
fault.
Verify that the ambient in the control
room is not below 2°C
Verify power to the TFB
There could be a mechanical problem
with the temperature sensor or with the
cable feeding the signal back to the TFB
Swap with the rectifier hardware to
identify the bad component
Inv ChB Low Temp
41
If the measured temperature Temp I Ch B C
(P552) is less than 2°C, and the drive is not
running, the drive will display this fault. This
is not enabled on most drives, and the
parameter is a high-level parameter.
Inv Heatsink OT
69
The temperature detection on the Inverter
Heatsink, connected to Channel A fiber optic
receiver RX7 on FOI-M-A, has exceeded
Inverter Heatsink Temperature Trip (P315).
Confirm actual temperature in
parameters is not higher than the trip
value If so, investigate the conditions of
the drive (ambient/ loading/ elevation /
ventilation/ filter status /heatsink
clogging)
Check the sensor and temperature
offline (ambient) for accuracy
Inv ChannelB OT
70
Not Normally Used - The temperature
detection on an Inverter Heatsink,
connected to fiber optic receiver RX7 on
FOI-M-B, has exceeded Inverter
Temperature Trip Channel B (P570)