Component Definition and Maintenance 6-113
7000 “B” Frame 7000-UM150I-EN-P June 2013
11. Press F2 [CONDITION] key. The cursor will move to the “=”
equal sign. This defines the trigger condition. Press up or down
arrow keys to select + sign as the trigger condition for our
example.
12. Press F3 [DATA] key. The cursor moves to the data field. In our
example we will enter 18 and then press Enter key.
13. Press F4 [RATE] key. The cursor moves to the rate field. Here
we will enter 0, which is the fastest sample rate (1 msec/sample)
and then press Enter key.