Commissioning 4-75
7000 “B” Frame 7000-UM150I-EN-P June 2013
CURRENT REGULATOR TUNED INCORRECTLY
CURRENT REGULATOR TUNED INCORRECTLY
11. Set parameter "Curreg bandwidth" to the normal value of 200
rad/sec. Confirm that the rise time of the current feedback is
now approximately 5 ms and that the overshoot is not excessive.
12. Set parameter "Idc ref step" to zero. The dc link current will
return to a steady level of 0.4 pu.
13. Stop the drive. Set parameters Operating Mode to Normal, and
Idc Command Test to 0.