User Manual User Manual
344 Rockwell Automation Publication 193-UM015B-EN-P - November 2013
Appendix B Parameter List
Command
(Continued)
169 Reserved
170 Reserved
Overload Setup 171 FLASetting Overload Full Load Current
Setting
UDINT 4 100 50 6553500 50 Amps
172 TripClass Trip Class Setting USINT 1 1 5 30 10
173 OLPTCResetMode Overload and PTC Trip Reset
Mode
BOOL 1 1 0=Manual
1=Automatic
0
174 OLResetLevel Overload Trip Reset Level USINT 1 1 0 100 75 %TCU
175 OLWarningLevel Overload Warning Reset Level USINT 1 1 0 100 85 %TCU
176 SingleOrThree Ph Single Phase = L1 & L2 BOOL 1 1 0=SinglePhase
1=ThreePhase
1
177 FLA2Setting Overload Full Load Current
Setting 2
UDINT 4 100 50 6553500 50 Amps
178 Reserved
179 Reserved
180 Reserved
181 Reserved
182 Reserved
Device Setup 183 TripEnableI Bitmask used to enable/disable
current based trips
UINT 2 1 Bit0= OverloadTrip
Bit1= PhaseLossTrip
Bit2= GroundFaultTrip
Bit3= StallTrip
Bit4= JamTrip
Bit5= UnderloadTrip
Bit6= CurrentImbalTrip
Bit7= L1UnderCurrTrip
Bit8= L2UnderCurrTrip
Bit9= L3UnderCurrTrip
Bit10= L1OverCurrenTrip
Bit11= L2OverCurrenTrip
Bit12= L3OverCurrenTrip
Bit13= L1LineLossTrip
Bit14= L2LineLossTrip
Bit15= L3LineLossTrip
3
184 TripEnabl eV Bitmask used to enable/disable
voltage based trips
UINT 2 1 Bit0= UnderVoltageTrip
Bit1= OvervoltageTrip
Bit2= VoltageUnbalTrip
Bit3= PhaseRotationTrp
Bit4= UnderFreqTrip
Bit5= OverFreqTrip
0
185 TripEnableP Bitmask used to enable/disable
power based trips
UINT 2 1 Bit0= UnderKWTrip
Bit1= OverKWTrip
Bit2= UnderKVARConTrip
Bit3= OverKVARConTrip
Bit4= UnderKVARGenTrip
Bit5= OverKVARGenTrip
Bit6= UnderKVATrip
Bit7= OverKVATrip
Bit8= UnderPFLagTrip
Bit9= OverPFLagTrip
Bit10= UnderPFLeadTrip
Bit11= OverPFLeadTrip
0
Group
Param
No.
Parameter Name Description Type
Data Size
(bytes)
Scale
Factor
Min Max Default Units