User Manual User Manual

156 Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Chapter 5 Protective Trip and Warning Functions
Table 149 - Over kW Inhibit Time (Parameter 382)
Under kW Trip
The E300 Electronic Overload Relay will trip with an Under kW indication if:
No trip currently exists
Under kW Trip is enabled
Current is present
Voltage is present
Under kW Inhibit Time has expired
The total real power (kW) is less than the Under kW Trip Level for a time
p
e
riod greater than the Under kW Trip Delay.
If the E300 Electronic Overload Relay trips on an under real power (kW), the:
TRIP/WARN LED status indicator will flash a red 2-long / 1-short blink
pa
ttern
Bit
0 in Power Trip Status (Parameter 6) will set to 1
Bit 0 in Device Status 0 (Parameter 20) will set to 1
Any relay outputs configured as a Trip Relay will open
Any relay outputs configured as a Control Relay will open
Any relay outputs configured as a Trip Alarm will close
Any relay outputs configured as a Normal Relay will be placed in their
Pr
otection Fault state (if so programmed)
Default Value 10
Minimum Value 0
Maximum Value 250
Parameter Type USINT
Size (Bytes) 1
Scaling Factor 1
Units Sec