Owner's manual

Chapter 6
Using the Pyramid Integrator Backplane
66
The following program shows how to trigger an inspection, and/or upload an
entire CVIM configuration for archiving and later downloading.
Rung #1 Triggers the CVIM to perform an inspection using toolset#1
upon false transition of 1N0:0/00.
Rung #2 Reads the integer value of gage 1 and places value in
1N0:02.
Rung #3 One shots 1N0:1/0 when 1N0:02 has a false to true
transition.
Rung #4 Sends message to read configuration:
Class: CVIM TW#1
Port:1
Internal Data Table Address: 0L9:0
External Data Table Address: >RC,CB*
All other message parameters are not critical.
Rung #5 One shots 1N0:1/3 when 1N0:0/3 has from false to true
transition.
Rung #6 Sends message to write configuration:
Class: CVIM TW#1
Port:1
Internal Data Table Address: 0L9:0
External Data Table Address: >W,CB*
All other message parameters are not critical.
Note: See Remote I/O (Chapter 3) for converting 16.16 data to a PLC
floating point value. Also see Chapter 3 for additional sample programs, and
Chapter 5 for RS232 commands.
The program begins on the next page.
Sample PLC5/250 Program