INSTALLATION MANUAL Manual
Chapter 12
Configuring Hardware for the MicroVAX
Information Processors
12-12
Table 12.D
System
Exerciser Display Codes
If this device: Displays this system exerciser
error code:
And: Then:
DZ 0000.0001 or 0000.4001 -- the device is good.
<> 0000.0001 or <>0000.4001 -- replace the module.
MEM XXXX.0001 XXXX is number of pages of
memory tested
the device is good.
<>XXXX.0001 -- replace the module.
HDC
1
XXXX.0001 no hard drives are connected the module is good.
<>XXXX.0001 no hard drives are connected replace the module
<>XXXX.0001 one or two drives are
connected and code
XXXX.0001 is displayed when
no hard drives are connected
one or both of the hard drives needs to be
replaced. Test each configured to module
separately to determine which (or both)
is bad.
TPC
1
8000.0001 the program loader
is connected
the program loader and module are good.
<>8000.0001 the program loader
is connected
replace the program loader.
XXXX.XXXX a program loader is not
connected
the module is good.
SCSIA
2
XXXX.0001 -- the device is good.
<>XXXX.0001 -- replace the module.
SCSIB
2
XXXX.0001 -- the device is good.
<>XXXX.0001 -- replace the module.
BPI
2
0000.0001 -- the dual port is good.
<>0000.0001 -- replace the module.
NI 0000.0001 -- the Ethernet port and cable are good.
<>0000.0001 -- replace the module.
1
MicroV
AX Information Processor (cat. no. 5730CPU1) only
.
2
MicroV
AX Information Processor EP or EE (cat. nos. 5731CPU1, CPU2) only
.
We recommend that you verify the industrial disk in your configuration
before you format or begin installing software on it. The verification
procedure will tell you if:
the disk has been formatted
the disk is in good condition
Verify
and Format Disk
(for 5730CPU1)