INSTALLATION MANUAL Manual

Chapter 11
Checking the Hardware
11-6
If you
have a:
If it is not:
It should be:Check the LED
labeled:
1
MEM
ERR will be on at initial power up until memory is cleared or downloaded.
2
These LEDs light after INTERCHANGE software has been loaded.
MicroVAX
Information
Processor
module
PASS/FAIL GREEN
cycle power by turning off the power from the power supply and then
turning it back on.
make sure the module is seated properly  see appendix A.
ENET CH A Flashing GREEN (If
connected and
communicating on the
Ethernet network)
make sure the connection to the Ethernet network is secure.
PROCESSOR OFF
2
BACKPLANE OFF
2
ENET CH B OFF
ERROR OFF
cycle power by turning off the power from the power supply and then
turning it back on.
make sure the module is seated properly  see appendix A.
it will blink the error code. Call support services.
BATTERY LOW OFF make sure the battery is inserted correctly in the battery holder.
KA module PASS/FAIL GREEN
make sure you turn on the power to the power supply.
cycle power by turning off the power from the power supply and then
turn it back on.
MEM ERR
1
OFF make sure the memory module is connected properly  see appendix A.
CH 1 Flashing GREEN
(if connected)
make sure the connection is secure.
CH 2 Flashing GREEN (if
configured as DH+ link)
CH 3 Flashing GREEN (if
configured as DH+ link)
OSI
Interface
Module
PASS/FAIL GREEN
cycle power by turning off the power from the power supply and then
turning it back on.
make sure you turn on the power to the power supply.
make sure the module is seated properly  see appendix A.
if cycling power doesn't work, replace the OSI Interface module.
MODE GREEN download the program image using AB MAP Station Manager.
ACTIVITY Flashing GREEN (If MAP interface is passing a message.)
MEM ERR OFF
cycle power by turning off the power from the power supply and then
turning it back on.
make sure you turn on the power to the power supply.
if cycling power doesn't work, replace the OSI Interface module.
BATT LOW OFF
make sure the battery is inserted correctly in the battery holder.
the lithium battery is weak and should be replaced.
COMM STATUS GREEN
if the LED is OFF, check 802.4 cable connections. Or check slot time.
if the LED is flashing RED, reset the module through the RS232 local
interface or through a power cycle.
if the LED is RED, reset the module through the RS232 local
interface or through a power cycle.
if resetting the module doesn't work, contact your local AB sales
office.