INSTALLATION MANUAL Manual

Chapter 9
Connecting the I/O Link
9-9
Figure 9.8
Connections
to RediP
ANEL Module
Bulletin 2705
RediPANEL Module
Blue
Shield
Clear
Blue
Shield
Clear
Blue
Shield
Clear
Bulletin 2705
RediPANEL Module
To
Scanner
150
16511
Figure 9.9 shows I/O link connections to a PLC interface module (cat. no.
3500-NA1) both as a middle device and as an end device on a link.
Connection is to the X4 terminal strip. Terminals 1, 2, 9, and 10 are
connected internally for line 1 (blue-insulation conductor). Terminals 3, 4,
7, and 8 are connected internally for the shield. Terminals 5 and 6 are
connected internally for line 2 (clear-insulated conductor). At each PLC
interface module, connect the shield drain wire of each cable segment to
give the shield continuity. However, never ground the shield at a PLC
interface module. At a PLC interface module connected as an end device
on a link, connect a 150-Ohm 1/4-Watt termination resistor across the
signal lines.
Figure 9.9
Connections
to PLC Interface Module
3500-NA1
PLC
Interface
Module
X4
1
2
3
4
5
6
7
8
9
10
Blue
Shield
Clear
Clear
Shield
Blue
X4
1
2
3
4
5
6
7
8
9
10
Clear
Shield
Blue
To
Scanner
3500-NA1
PLC
Interface
Module
150
16512
Connecting to a PLC
Interface Module