Safety Interface M8200 Relay Module Owner's manual
83
75035-119-01(A) / K832 / 26-09-00 © Rockwell Automation • Milwaukee, Wisconsin • All rights reserved
Operating instructions
M 8200
GB
6 Technical Data
min. typ. max.
General
Protection class I
Housing protection IP 65 (control cabinet, standard rail)
Supply voltage U
V
19.2 V 24 V 28.8 V
Residual ripple
1
)5 V
SS
Power concumption (no load) 0.3 A (6 W)
Inputs Command unit Start key
T 13, T 14 NO contact
Command unit actuation time period 30 ms
Contactor monitoring
T 21, T 22 contactor monitoring NC contacts in series
Permissible contactor drop-off time No restrictions
Permissible contactor response time 200 ms
Sensor signal T 3, T 4 Two-channel
Input resistance (active) 606 Ω 674 Ω 742 Ω
Signal active at 17.6 V U
V
Signal LOW at 0 V 2.4 V
Time period tolerance between T 3 and T 4 15 ms
Outputs
Response time 15 ms
2
)
Switching current < 0.1 mA
3
)4 A
Switching voltage AC / DC 240 V AC /
60 V DC
Switching AC / DC 1200 VA /
50 W
Mech. life expectancy (switch actions) 10
7
Elec. life expectancy (switch actions) 10
9
Delay on Energisation (NO contacts) 40 ms
Delay on Energisation (NC contacts) 15 ms
Supply voltage U
V
Connection Pluggable strip terminal
Cable cross section 2.5 mm
2
Load capacity of terminals
(C 1 ... 4, D 1 ... 4) 2.5 A
Operating data
Safety category Type 4
Tested to pr EN 50 100 Part 1 and 2
Ambient operating temperature 0 °C +55 °C
Storage temperature –25 °C + 75 °C
Relative humidity (non condensing) 15 % 95 %
Vibration specification 5 g, 10 ... 55 Hz as per IEC 68-2-29
Shock resistance 10 g, 16 ms as per IEC 68-2-29
Dimensions (W x H x D) 152 x 73 x 118 mm
3
Electrical Connections
Chapter 6