Safety Monitoring Functions Chapter 9
Figure 80 - Example Schematic for Two OSSD
Dual Channel N.C./N.O.
The N.C./N.O. configuration applies the diversity concepts, where one contact
is open and the other contact is closed. The contact, while in an open state,
cannot be welded closed. The CR30 turns off its safety outputs when either
channel changes state. Both channels must change state for proper performance.
Figure 81 - Example Schematic for N.C./N.O. without Test Pulse
Figure 82 - Example Schematic for N.C./N.O. with One Test Pulse
Figure 83 - Example Schematic for N.C./N.O. with Two Test Pulses
If a short circuit occurs on terminal 12 to 24V, the CR30 turns off its safety
outputs within 35 ms. Remove the fault and cycle the contacts to clear the fault.