Safety Relay User Manual Owner's manual
Rockwell Automation Publication 440C-UM001C-EN-P - November 2014 67
Safety Monitoring Functions Chapter 9
Figure 72 - Wiring Connection for a Type IIIC Two-hand Control with Test Pulses
The timing diagram for the two-hand control is shown in Figure 73. The Type
IIIA uses only the N.O. contact of the button. The Type IIIC uses both the N.C.
and the N.O. contacts.
Figure 73 - Two-hand Control Timing Diagram
Description Description
1 Hand 1 button is pressed. 5 Hand 2 button is pressed.
2 Hand 2 button must be pressed within 500 ms
for the output logic to turn ON.
6 Hand 1 button must be pressed within 500 ms
for the output logic to turn ON.
3 Releasing either hand button causes the logic
output to turn off.
7 Releasing either hand button causes the logic
output to turn off.
4 Both hand buttons must be released to start a
new cycle.
8 Both hand buttons must be released to start a
new cycle.
+24V DC
24V Com
AB
05
CR30
020100 03 04
A1 15 20 2116
06
18A2
07
19
08 10 11
12 13 14
09
17
Logic Output
Hand 1 N.C.
Hand 1 N.O.
Hand 2 N.C.
Hand 2 N.O.
HI
LO
HI
LO
HI
LO
HI
LO
HI
LO
1 432 5 6 7 8
must be less than 500ms