Safety Relay User Manual Owner's manual
58 Rockwell Automation Publication 440C-UM001C-EN-P - November 2014
Chapter 9 Safety Monitoring Functions
Figure 53 - Example Schematic for 4-Sensor Muting
For simplicity, the power and ground connections of the light curtain and muting
sensors are not shown. The light curtain and muting sensors must have the same
reference (24V Com) as the CR30 for proper operation.
For proper operation, the muting sensors are on (normally closed) when not
muting, and the light curtain OSSD outputs are also on (the light curtain is
clear).
Figure 54 - Muting Time for 4-Sensor Muting
+24V DC
Light Curtain
24V Com
MS1
MS2
A
OSSD A
OSSD B
MS3
MS4
Override
Contactors
for Conveyor Power
Muting Lamp
05
CR30
020100 03 04
A1 15 20 2116
06
18A2
07
19
08 10 11
12 13 14
09
17
K2
K1
LC
Muting sensor 1 (4)
Muting sensor 2 (3)
Muting sensor 3 (2)
Muting sensor 4 (1)
Muting lamp
t > 30ms
t > 30ms
t > 30ms
t > 50ms
30ms <= t
t < synchronization
time
30ms <= t
t < synchronization
time
t < muting time
muted