Safety Relay User Manual Owner's manual

38 Rockwell Automation Publication 440C-UM001C-EN-P - November 2014
Chapter 5 Pulse Testing
Then a sequence occurs in which each output is individually tested twice. The
test pulse is 50 μs wide. The test pulses occur every 250 ms and switch to the next
output configured with testing.
Figure 22 - Test Pulse Sequence
T
erminal 13
Terminal 12
24V
0V
24V
0V
T
erminal 20
T
erminal 21
24V
0V
24V
0V
0 250 500ms