User guide
1
Installation Instruction
ClearSight RightSightt PHOTOSWITCH
R
Photoelectric Sensors
Optical
Sensing Mode Clear object
Sensing Distance 1.2m
Field of View
1.5_
Transmitting LED Visible Red 660nm
Sensitivity Adjustment Yes, single turn
Electrical
Supply Voltage 10.8--30V DC (DC models), 21.6--264V AC/DC
(AC/DC models)
Current Consumption 35mA maximum
Protection False pulse on power up, reverse polarity, output
short-circuit protection, overv oltage
Output Type Dual NPN and PNP (DC models),
MOSFET (AC/DC models)
Output Load Voltage/Current 100mA @ 30V DC (DC models), 100mA @ 264V
AC/DC (AC/DC models)
Output Energized Light/Dark operate by catalog number
Output Response Time 0.5ms (DC models), 1ms (AC/DC models)
Mechanical
Housing Material Mindel
Lens Material Acrylic
Indicators Yellow: Output, Green: Power, Orange: Margin/SCP
Environmental
Operating Temperature
-- 2 5 _Cto+70_C(--13_F to +158_F)
Operating Environment NEMA 3R, 4X, 6P; IP67 1200psi washdown
Vibration 10--55Hz, 1mm amplitude, Meets or exceeds IEC
947--5--2
Shock 30G with 1ms pulse duration, Meets or exceeds IEC
947--5--2
Relative Humidity Up to 95%
Approvals UL, CSA, CE marked for all applicable directives
Accessories
Supplied 92--90 Reflector
18mm locknut
Optional 889D--F4AC--2 cordset (DC models),
889R--F4AEA--2 cordset (AC/DC models)
60--2649 Tilt/Swivel Mounting Bracket
60--2657 Mounting bracket, metal
LED Function Tables
DC Models
Label Color State Status
Output Yellow
OFF Output de energized
ON Output energized
Flashing Output SCP active
Margin Orange
OFF Margin < 2.5
ON Margin >2.5
Flashing Output SCP active
Power Green
OFF Sensor not powered, output active, SCP active
ON Sensor powered
AC/DC Models
Label Color State Status
Output Yellow
OFF Output de energized or SCP active
ON Output energized
Margin Orange
OFF Margin < 2.5
ON Margin >2.5
Flashing Output SCP active (short circuit)
Power Green
OFF Sensor not powered
ON Sensor powered or SCP active
Short-Circuit Protection Feature (SCP)
RightSight photoelectric sensors provide short-circuit protection (SCP) on the
output leads. This feature is intended to protect the sensor from damage in
the event that the output load is shorted to ground. If this condition does
occur, the SCP will activate and the orange and yellow LEDs will flash (for
AC/DC models only the orange indicator will flash) until the source of the short
isremoved(powermustberesetforAC/DC models). The SCP limits are set
to 100mA over the entire voltage range.