LonWorks Module for VTAC 7 Drives
9.1.1 Module Status LED
9.1.2 Service LED
9.1.3 Wink LED
Table 9.1 – Module Status LED: State Definitions
LED State Cause Corrective Action
Solid green Normal operation/power on None required.
Flashing
green
Initialization of AnyBus/VTAC 7
interface
None required.
Flashing red Recoverable fault:
• 4 Hz:
• 2 Hz: Heartbeat timeout
received.
• 1 Hz: Node is offline.
• 4 Hz: Check that P.061 is set to
1 for full access to all drops.
• 2 Hz:
• 1 Hz:
Solid red Unrecoverable fault (hardware
error).
Replace module.
Table 9.2 – Service LED: State Definitions
LED State Cause Corrective Action
Off This node is configured and
installed in a network.
None required.
Flashing
green
This node has an application, but
it is not yet installed in a network
(unconfigured).
Configure the application.
Solid green This node is unconfigured and
has no application. Indicates
errors detected by the Neuron
self-test routine.
Configure node and load application.
Table 9.3 – Wink LED: State Definitions
LED State Cause Corrective Action
Off Normal state. None required.
Flashing red A wink command is received on
the LonWorks network.
None required.