User Manual

8-2
LonWorks Module for VTAC 7 Drives
8.3 Stopping the Drive
The drive will stop using the stop mode selected in parameter P.025 if
any
of the
following conditions are met:
NviSpeedStpt.state is set to any value but 1
The node is brought offline
RQ_DISABLED is requested in nviObjRequest
8.4 Setting the Frequency
The actual value written to the LonWorks module =
(nviDrvSpeedStpt*0.5*nviDrvSpeedScale*0.005*nciNmlFreq*100) / (100*100)
Notes for above equation:
Multiplied by 0.005 and 0.5 to scale the two LonWorks format values
Nominal frequency is the base for scale and setpoint percent values
Multiplied by 100 to fit LonWorks module format.
Divided by (100*100) because the setting frequency is multiplied by two percent
values.
Refer to chapter 7 for information about nviSpeedStpt and nviSpeedScale.
8.5 Writing Values to a VTAC 7 Register
To write a value to a VTAC 7 register:
Step 1. Change register in nciWriAddr.
Step 2. Change value in nciWriValue.
Changing the value in nciWriValue triggers the writing to a register in the LonWorks
module. Changing the address alone will not perform a write sequence.
To verify that the LonWorks module has accepted the value written to it, read it back
by setting nciRdAdr to the corresponding DP RAM feedback register. See Appendix B
for a list of registers.
NviSpeedScale NviSpeedStpt.value NviSpeedStpt.state Resulting Speed
0% 0% 1 0 Hz
100% 0% 1 0 Hz
0% 100% 1 0 Hz
150% 100% 0 (Normal) Stop
150% 100% 1 1.5*1.0*Nomfreq
-75% 100% 1 -0.75*1.00*Nomfreq
150% 50% 1 1.5*0.50*Nomfreq