User Manual

7-12
LonWorks Module for VTAC 7 Drives
.
Current Limit
Definition: network input config SNVT_lev_percent nciCurLimit
Explanation: Sets the current limit in percent of motor nameplate amps.
Default: Read from drive
Generic Parameter Register Setting, Write
Definition: network input config SNVT_count nciParWriAddress
Explanation: Selects register to write to in the drive. The first digit is the drive
drop number. The remaining digital represent the register. For
example, 203 = drop 2, register 3. See section 8.5 for more
information
Range: 000-063 = Drop 0
100-163 = Drop 1
200-263 = Drop 2
300-363 = Drop 3
Parameter Value, Write
Definition: network input config UNVT_sj300 nciParWriValue;
Explanation: Value that is written to nciParWriAddress. See section 8.5 for
more information.
Range: 000-063 = Drop 0
100-163 = Drop 1
200-263 = Drop 2
300-363 = Drop 3