User Manual Owner's manual
Rockwell Automation Publication 290D-UM001A-EN-P - June 2012 99
Bulletin 290D/291D/294D Programmable Parameters Chapter 4
Bit
Function
1514131211109876543210
——————————————— X
OverloadTrip
—————————————— X — PhaseLossTrip
————————————— X —— UnderPowerTrip
———————————— X ———
SensorShortTrip
——————————— X ———— PhaseImbalanceTrip
—————————— X ————— NonVolMemoryTrip
————————— X —————— Reserved
———————— X ——————— JamTrip
——————— X ———————— StallTrip
—————— X —————————
UnderloadTrip
——— X X X —————————— Reserved
—— X ————————————— OutputShortTrip
— X —————————————— UserDefinedTrip
X ———————————————
HardwareFltTrip
The highlighted functions are enabled by default.
WarningStatus
This parameter provides the current
warning condition.
Parameter Number 43
Access Rule GET
Data Type WORD
Group Trip Status
Units —
Minimum Value 0
Maximum Value 0xC295
Default Value
Bit
Function
1514131211109876543210
——————————————— X OverloadWarning
—————————————— X — Reserved
————————————— X ——
UnderPowerWarn
———————————— X ——— Reserved
——————————— X ———— PhasImbalanceWarn
————————— X X ————— Reserved
———————— X ——————— JamWarning
——————— X ———————— Reserved
—————— X ————————— UnderloadWarning
——XXXX—————————— Reserved
— X —————————————— UnswitchedPwrWarn
X ——————————————— ConfigWarning